Comprehensive power quality data collection. Revenue-accurate meter to 0.2%. Monitors four voltage and four current channels for each electrical cycle. Provides 1024 samples across eight channels every cycle. Virtual wiring correction. Sag/swell detection. Single cycle metering. Measures up to the 127th harmonic. View Data and Configure through Integrated Web Page. Configurable alarms for up to 10 events. Four inputs for WAGES (water, air, gas, electricity, steam) data collection. Four outputs for connection to SCADA or control systems. Native EtherNet/IP™ communication port included. Option for a second communication port. Integration with FactoryTalk™ EnergyMetrix.