Supply and install Lumacell® IPL Series of fluorescent fixtures as specified. The luminaire shall operate from 120VAC to 277VAC and use high quality instant start or 3-step programmed rapid start high efficiency electronic ballasts. The housing and lens shall be constructed of UV- stabilized industrial grade vandal-resistant polycarbonate. A durable formed gasket shall be provided between the enclosure and the lens and shall be designed specifically for hostile environments. The reflector shall be made of highly specular material and formed to maximize light output efficiency. All parts shall be corrosion resistant. A metal plate used to retain the ballast and reflector also serves to dissipate heat, therefore lengthening ballast life. Lamps shall be as specified, either T8 or T5 HO linear fluorescent lamps, 32W or 54W. The lamps shall not be supplied with the luminaire. Models with an inverter from the RSFSP/AM series and illuminate one or two lamps during emergency operation for at least 90 minutes upon AC failure. During power outage, dual voltage source (AC/DC) models with an inverter from RSF series, shall illuminate one lamp while the DC voltage is present. The fixture shall be CSA approved and meet IP65 requirements. Emergency fixture shall have one year warranty. Non-emergency fixture shall have five year warranty The inverters of RSF Series shall be CSA approved. The inverters of RSFSP/AM Series shall be CSA or cUL approved.